Industrial line starts at 26.8.x. Older 25.x — contact MOIZ or your supplier. Prefer the latest JS decoder on your application.
Full re-commissioning in Toolbox (config + calibration) and decoder refresh. Toolbox prompts a firmware upgrade when the connected device is below the 26.8 line.
26.11.0
2026-10-01Added
- PRESS_A port — gauge pressure (psi) + sensor temperature (°C); decoded keys
pressA_*/pressA_*_temp
Requires Toolbox with PRESS_A support · decoder family 26.11+ (harvestree_decoder.js)
26.10.0
2026-08-18Added
- SOUND_A port — A-weighted sound level (dB SPL); decoded key
soundA_*(dB, one decimal)
Requires Toolbox 3.2.0+ · decoder family 26.10+ (harvestree_decoder.js)
26.9.0
2026-08-17Added
- ACCT port — AC current via CT coil (333 mV RMS secondary); decoded keys
acct_*/acct_*_hz - LoRaWAN region IN865 (select in Toolbox)
- US915 / AU915 — additional channel plans (full band + hybrid sub-bands 2..8); factory hybrid sub-band 1 unchanged
Changed
- Vibration — measurement uses mean subtraction; the vibration calibration offset no longer changes the reported value (re-check site calibration if you relied on that offset)
- Downlink —
FACTORY_RESET, product tag, and connector tag are no longer accepted over LoRaWAN (USB / maintenance only). Field downlink remains GET/SET param, GET_VERSION, GET_HW_VERSION, RESET
Requires Toolbox 3.1.0+ · decoder family 26.9+ (harvestree_decoder.js)
26.8.4
2026-06-09Maintenance release — no customer-visible change to operation, payloads, configuration, or downlink.
26.8.3
2026-06-05Changed
- OTAA join — while storage voltage is below the configured minimum, the device re-checks every 300 s (was 20 s) and also pauses join retries (less load while energy builds). USB commissioning stays available during the wait
26.8.2
2026-05-19Maintenance release — no customer-visible change to operation, payloads, configuration, or downlink.
26.8.1
2026-04-30Added
- Modes — Monitoring, Alarm (sync + async), Idle, Modbus RTU slave
- Ports — expanded measurement set (magnetic, current ΔU / magnetic, differential + external amp, AC/RMS paths); dual-band vibration uplink
- Calibration — per-port model adapted for simplified Toolbox screens (offset / LUT)
- LoRaWAN downlink — GET/SET param, GET_VERSION, GET_HW_VERSION, RESET
- Regions — AU915 and AS923-1
Changed
- Same parameter rules in Toolbox and over downlink
- Alarm HIGH/LOW include the threshold — no hysteresis (filter in your application if needed)
- OTAA join waits until storage voltage ≥ configured minimum
Fixed
- On-board temperature in uplink metadata correct below 0 °C
- Vibration calibration offset consistent in mV